Description
KEY FEATURES
- Components:
165 mm (6.5 in) high output driver with polypropylene cone and butyl rubber surround
19 mm (0.75 in) soft-dome liquid-cooled tweeter - EN 54-24 Compliant for Life Safety Applications
- Blind-mount backcan for quick and easy install
- Combined 70V/100V and low impedance direct operation
50 Watts at 8 nominal setting
30W multi-tap at 70V/100V - 62 Hz 20 kHz bandwidth with wide 110 coverage
- High 91 dB sensitivity for high maximum SPL
DESCRIPTION
Control 16C-VA is a full-range, EN54-24 certified ceiling speaker consisting of a 165 mm (6.5 inch) high tech cone driver and a 19 mm soft-dome liquid cooled tweeter mounted in a vented, paintable baffle made of UV resistant UL94-V0 and UL94-5VB flammability-rated material, with a pre-attached blind-mount backcan for quick and easy installation. The speaker is designed to provide excellent sound quality for a wide variety of medium to high volume applications such as music cafes, business music systems, retail stores, music/paging systems, airports, reception/ waiting rooms, lounges, courtrooms, convention centers, hotels, educational facilities, and more. The speaker delivers consistent sound quality for listeners located both off and on axis.This loudspeaker is EN 54-24 Compliant for life safety applications.
SPECIFICATIONS
Frequency Range (-10dB) | 62 Hz 20 kHz |
Frequency Response (3 dB) | 96 Hz 15 kHz |
Power Rating | IEC System Long-Term Ratings (low-Z direct): 100 Watts Continuous Program Power 50 Watts Continuous Pink Noise (200W peak), 100 hrs |
Rated Noise Power | 30W (30W tap) |
Rated Noise Voltage | 70V/100V (with 70V/100V tap settings) |
Sensitivity | 91 dB (1kHz – 16 kHz) |
EN54 Sensitivity (@ 4m) | 77 dB (per EN54-24 spectrum and measurement conditions at 4 meters). |
Coverage Angle | 110 conical |
Coverage Angles(by Frequency) Conical (Vertical & Horizontal) | 500 Hz: 1801000 Hz: 1602000 Hz: 1554000 Hz: 92 |
Reference Axis | Specification and measurement reference is directly on-axis vertically and horizontally, directly below the speaker as speaker it is installed in the horizontal ceiling plane |
Directivity Factor (Q) | 7.8 |
Directivity Index (DI) | 8.2 dB |
Maximum SPL (1m) | 108 dB (low-impedance, 116 dB peak) 106 dB (top 70V/100 tap) EN54: 91 dB (4m, top 70/100V tap) |
EN54 Max SPL (@ 4m) | 91 dB (per EN54-24 spectrum and measurement conditions, 30W tap, at 4 meters) |
Impedance | 8 ohms (in direct/bypass 8 ohm setting); EN54 nominal impedance 7 ohms (based on min Z of 5.7 ohms at 11.2 kHz) 3.8W@70V; 7.5W@100V Tap: 1333 7.5W@70V; 15W@100V Tap: 667 15W@70V; 30W@100V Tap: 333 30W@70V; N/C@100V Tap: 166 |
Transformer Taps | 30W, 15W, 7.5W @ 70V or 100V (plus 3.8W @ 70V only) |
Crossover Network | 12 dB/oct (2nd order) low-pass to LF driver, 12 dB/oct (2nd order) high-pass to HF driver |
Fuse | Thermal Fuse, open temperature 152 degrees C, Rating >= 10A @ 250VAC |
Drivers | LF Driver: 165 mm (6.5 in) HF Driver: 19 mm (3/4 in) |
Connections | Input +, Input -, Earth (connected to backcan). Ceramic with brass inserts (3.2 mm/0.126 in opening), accommodates 2.5 sq mm / 12 AWG wire. |
Gland Nut/Strain Relief | Accommodates round jacketed cables 4.0 mm (0.16 in) through 9.0 mm (0.36 in) |